Permit Number: T10CM02118
Parcel: 12801007A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02118
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2010 STEVE SHIELDS ZONING REVIEW Approved
08/02/2010 JASON GREEN ENGINEERING REVIEW Approved
08/02/2010 ERIC NEWCOMB ADA REVIEW Passed
08/02/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-4; ELEVATIONS: THERE ARE SEVERAL ARROWS WITHOUT REFERENCE TO VERBIAGE. VERIFY.
2. SHEET A-4; ELEVATIONS: THE REQUIREMENTS OF THE CITY OF TUCSON REQUIRE A MINIMUM OF 3/32" LETTERING HEIGHT. REVISE.
3. SHEET A-0; BUILDING CODE DATA: THE ACCESSIBILITY CODE USED FOR THIS PROJECT SHOULD BE ICC/ANSI A117.1-2003, NOT ADAAG.
08/02/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
08/02/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/03/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Ventilation for restrooms in public spaces requires a minimum of 75 CFM of mechanical exhaust per water closet or urinal. Revise your calculations and balance accordingly. Reference: Table 403.3, IMC 2006.
08/03/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
08/03/2010 ROBERT SHERRY WATER REVIEW Approved
08/03/2010 MARTIN BROWN FIRE REVIEW Denied 1. Notes on PG A-0 for sprinkler system need plans and permits for adding 1 head or relocating more than 5 heads. permit only for less than 5 head relocate.
2. Pg A-3 under general notes #14 door hardware is A-6.
3. Pg A-6 under door notes #5 only allowed on front main door.
08/03/2010 GERRY KOZIOL WWM REVIEW Passed
08/03/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
08/03/2010 DELMA ROBEY OUT TO CUSTOMER Completed