Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM02106
Parcel: 99999999C

Review Status: Completed

Review Details: CELL TOWER/ANTENNAS

Permit Number - T10CM02106
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2010 BRIAN HEFFERNAN COMMUNICATIONS REVIEW Denied need communication info sheet
08/06/2010 MARTIN BROWN FIRE REVIEW Approved
08/06/2010 Michael Wyneken PLANNING-CITY HALL REVIEW Denied The proposed enclosure creates a dead space between it and the nearby patio wall, which violates safe by design principles because people can hide in the dead space. Looking to mitigate this issue.
08/12/2010 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: T10CM02106
6921 E TANQUE VERDE RD (1st Review)

TRANSMITTAL DATE: August 12, 2010

1. The Cell Tower plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. The plan must be approved and stamped by the Special Exception Section prior to approval by Zoning.

3. Zoning will re-review the Cell Tower plan on the next submittal to insure compliance with the approved Special Exception process. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\celltower\t10cm02106.doc
08/12/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET 03 (ENLARGED SITE PLAN); SHEET 12 (DETAIL 1): COORDINATE THE DIMENSIONS FROM THESE SHEETS FOR THE LEASE AREA BLOCK WALLS.
2. SHEET 12 (DETAIL 4); STRUCTURAL CALCULATIONS: PROVIDE THE BASE PLATE DESIGN IN THE CALCULATIONS AND ON DETAIL 4.
3. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
08/25/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/07/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
09/07/2010 SUE REEVES REJECT SHELF Completed