Permit Number: T10CM02102
Parcel: 13316024P

Address:
6350 E GRANT RD

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T10CM02102
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Reprint the pages to include the information at the bottom of the sheets.
01/19/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Reprint the pages to include the information at the bottom of the sheets.
2. Provide ventilation calculations for the areas served by HP-15 and HP-16.
01/19/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/25/2011 CINDY AGUILAR APPROVAL SHELF Completed
01/25/2011 CINDY AGUILAR OUT TO CUSTOMER Completed