Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM02102
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/12/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 10/12/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/20/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Comment not resolved; no new documents have been submitted. Coordinate the structural elements of detail 1/P4.1 (WH-2) with the design of the supporting structure as shown in detail 28/S1.03. Reference: Section 307, IPC 2006. |
| 10/20/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Comment not resolved; no new documents have been submitted. Revise the submitted energy code calculations to use the correct location (Pima County < 4,000 feet, not Marana). Coordinate the calculations with the drawings and the building specifications (e.g. the specifications show three glazing types but the calculations show only two and there are multiple exterior wall types but only one is shown on the envelope calculations). The mechanical compliance certificate on sheet M5.1 is not an issue. Reference: Sections 102.1 and 104.2, IECC 2006. |
| 10/21/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/22/2010 | SREEVES1 | WWM | REVIEW | Denied | NEED TO INDICATE ON PLAN THAT ALL FLOOR TROUGH AND TRENCH DRAINS ARE TO BE UNDER ROOF OR COVER ALSO CURBED AND/ORPAVEMENT PITCHED SO NOT TO ALLOW RAIN WATER TO FLOW INTO SANITARY SEWER. NEED IWC REVIEW AND APPROVED FOR SAND/GREASE INTERCEPTORS CONTACT TOM TOMCHAK 443-6200 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/28/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 10/28/2010 | SUE REEVES | REJECT SHELF | Completed |