Permit Number: T10CM02102
Parcel: 13316024P

Address:
6350 E GRANT RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02102
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2010 MARTIN BROWN FIRE REVIEW Denied Please include the following fire sprinkler design criteria to the plans.
1. Flow data (static pressure, residual pressure, GPM)
Available from the Fire Department (520) 837-7029 or 837-7030.
2. The standard to be used in development of sprinkler system. (NFPA 13, NFPA 13R, or NFPA 13D)
3. The hazard classification of the building, including any special hazards.
4. The density required of the water supply.
Indicate on plans hazard classification for specific areas.
Also, note on cover sheet states "sprinklers throughout".
Please confirm that this means sprinklers under every covered structure.
09/23/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT 1; SHEET CS (PLUMBING FIXTURE COUNT); SHEET CA1.00 (TOTAL OCCUPANT LOAD): THE OCCUPANT LOAD USED TO CALCULATE THE PLUMBING FIXTURES (SHEET CS) DOES NOT MATCH THE OCCUPANT LOAD LISTED ON SHEET CA1.00. THIS WAS NOT CLARIFIED.
2. PREVIOUS COMMENT 5; DEFERRED SUBMITTALS: IT WAS NOT VERIFIED WHETHER THE DRAWINGS FOR THE PARTS AREA (LEVELS 2 AND 3) SHOULD BE INCLUDED IN DEFERRED SUBMITTALS.
3. PREVIOUS COMMENT 6; DEFERRED SUBMITTALS: IT WAS NOT VERIFIED WHETHER THE DRAWINGS FOR THE OPEN DISPLAY CANOPY SHOULD BE INCLUDED IN DEFERRED SUBMITTALS.
4. PREVIOUS COMMENT 16; SHEET AS1.02; DETAIL 11: STRUCTURAL CALCULATIONS WERE NOT PROVIDED FOR THE SITE WALL AND FOOTING DESIGN.
5. PREVIOUS COMMENT 22; SHEET S3.01 (FRAMING PLAN): IT WAS NOT VERIFIED WHETHER STRUCTURAL CALCULATIONS WERE PROVIDED FOR THE DESIGN OF THE W16X40 BEAM AT APPROXIMATE GRID H.0.
6. PREVIOUS COMMENT 23; SHEET S3.01 (FRAMING PLAN); HI/LOW B4 BEAMS BETWEEN GRIDS D.0, E.0, AND F.0: IT WAS NOT VERIFIED WHETHER CALCULATIONS WERE PROVIDED FOR THE DESIGN OF THESE BEAMS.
7. PREVIOUS COMMENT 25; SHEET S3.01 (FRAMING PLAN); SHEET S5.04 (DETAIL 277): IT WAS NOT VERIFIED WHETHER THE DETAIL WAS CORRECTLY SHOWN.
8. PREVIOUS COMMENT 37; SHEET S7.01; STEEL STAIR BEAM SCHEDULE: IT WAS NOT VERIFIED WHETHER THE SSB3 MEMBER WAS SIZED CORRECTLY.
9. PREVIOUS COMMENT 38; GENERAL: A SPECIAL INSPECTION WAS NOT ADDED TO THE CERTIFICATE FOR SITE PREPARATION, FOUNDATION, AND EXCAVATION.
10. PREVIOUS COMMENT 39; GENERAL: WRITTEN RESPONSES WERE NOT PROVIDED FOR ALL REVIEW COMMENTS.
09/24/2010 ERIC NEWCOMB HC REVIEW Approved
09/24/2010 JASON GREEN ENGINEERING REVIEW Approved Building plan is approved, however final approval stamp will be placed on the building plan set that is stamped approved by all other sections, i.e. Fire, Structural, etc.
10/01/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. Revise the submitted energy code calculations to use the correct location (Pima County < 4,000 feet, not Marana). Coordinate the calculations with the drawings and the building specifications (e.g. the specifications show three glazing types but the calculations show only two and there are multiple exterior wall types but only one is shown on the envelope calculations). The mechanical compliance certificate on sheet M5.1 is not an issue. Reference: Sections 102.1 and 104.2, IECC 2006.
10/01/2010 GERRY KOZIOL WWM REVIEW Denied NEED TO INDICATE ON PLAN THAT ALL FLOOR TROUGH AND TRENCH DRAINS ARE TO BE UNDER ROOF OR COVER ALSO CURBED AND/ORPAVEMENT PITCHED SO NOT TO ALLOW RAIN WATER TO FLOW INTO SANITARY SEWER.
NEED IWC REVIEW AND APPROVED FOR SAND/GREASE INTERCEPTORS CONTACT TOM TOMCHAK 443-6200
10/01/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Coordinate the structural elements of detail 1/P4.1 (WH-2) with the design of the supporting structure as shown in detail 28/S1.03. Reference: Section 307, IPC 2006.
10/01/2010 SREEVES1 ZONING REVIEW Passed
10/07/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
10/07/2010 DELMA ROBEY OUT TO CUSTOMER Completed