08/11/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM02098
1082 E Ajo Wy # 100
TI Office


Electrical plans denied for following:

1. The service entrance conductors listed as 4-# 750 kcmil aluminum are rated for 385 amps on a 1000 amp main ?
2. Circuit A-21 on power plan E-2, not in schedule,no load.
3. Circuit B-35 for HVAC receptacles sheet E-2, shown as half leg of Water Heater in panel schedule.
4.Lighting plan sheet E-2, showing D circuits 2,4,6, should be "B" for panel B.
5. Lighting plan shows two A-2v circuits.
6. Lighting plan shows a circuit for D-86, should be B-6.
7. Sheet E-2 shows circuit A 30,32, however are blank spaces in panel schedule.
8. Power plan sheet E-2 circuit B-35 roof receptacles should be A-35

Ray T Majuta
ELect Pln CK
PDSD< City of Tucson,
8/12/10