Permit Number: T10CM02094
Parcel: 11460019B

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02094
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. Revise the outside air flow rate in keynote #1 on sheet M1.1 to agree with the outside air calculations (it still calls for 285 CFM of outside air).
09/10/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide a design for the mounting shelf for the water heater. Reference: Sections 310.0 and 314.5, UPC 2006.
2. Clarify the note in the Plumbing Fixture Schedule regarding the water hammer arrestors; how will the installation of a reduced-pressure principle backflow preventer (RPBP) have any positive effect on water hammer if the water pressure exceeds 85 PSI. Did you mean to refer to a pressure reducing valve (PRV)? Reference: Section 608.2, UPC 2006.
3. Comment not resolved; a vacuum relief valve is not the same as a vacuum breaker. Installation of the required vacuum relief valve shall be in accordance with the manufacturer's instructions, i.e. there shall be no valves between the vacuum relief valve and the storage tank. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
4. Comment not resolved; see waste and vent diagram "C". Provide cleanouts sized per Section 707.11, UPC 2006.
5. Comment not resolved. With respect to waste and vent diagram "D", the specified interceptor is designed for top access to the removable sediment bucket; install per the manufacturer's instructions to provide sufficient maintenance access. Reference: Sections 310.4 and 1001.1, UPC 2006.
09/20/2010 RONALD BROWN HC REVIEW Approved
09/20/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
09/29/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/08/2010 GERRY KOZIOL WWM REVIEW Approv-Cond fees caluated w/o credit evaluation

Final Status

Task End Date Reviewer's Name Type of Review Description
10/12/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
10/12/2010 SUE REEVES REJECT SHELF Completed