Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM02094
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
07/30/2010 | TERRY STEVENS | ZONING | REVIEW | Approved | |
07/30/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | RECEIVED | |
07/30/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/10/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL 1. As per COT PDSD standards, minimum lettering type is 3/32" in height. The following sheets have lettering types less than 3/32": A1.1, A-2, H-1 and E5.1. Please revise all types to 3/32" minimum and resubmit SHEET H-1 2. At detail 13, change the mounting height to the bottom of the main sign from 6'-8" to 7'-0" 3. As per Section 1210.2 Walls. "Walls within 2 feet (610 mm) of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet (1219 mm) above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture." a. the scheduled enamel paint is not hard and is adversly effected by moisture. END OF REVIEW |
08/10/2010 | RONALD BROWN | ZONING HC | REVIEW | Denied | Reference Building Comments |
08/11/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the outside air flow rate in keynote #1 on sheet M1.1 to agree with the outside air calculations. 2. Show the location of keynote #5, M1.1, on the drawing. Reference: Section 106.3.1, IMC 2006. 3. Revise the size of the condensate drains in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson. 4. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. exhaust fans shall operate whenever supply air is being introduced into the restroom). Reference: Section 403.2.1 (4), IMC 2006. |
08/11/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/12/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. The plans have been reviewed to the 2006 UPC; provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC. 2. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for business occupancy (e.g. a service sink). 3. Provide a design for the mounting shelf for the water heater. Reference: Sections 310.0 and 314.5, UPC 2006. 4. Clarify how the temperature of the hot water supply to the public lavatories is to be controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006. 5. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. clothes washer). Reference: Section 609.10, UPC 2006. 6. Verify that the reduced pressure backflow preventer located in room 114 conforms to the access and clearance requirements of Section 603.3.4, UPC 2006. 7. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006. 8. Provide cleanouts sized per Section 707.11, UPC 2006. 9. Revise waste and vent diagram "C" to correspond with the plumbing plan. Reference: Section 103.2.3, UPC 2006. 10. With respect to waste and vent diagram "D", no more than one trap shall be installed on a trap arm; the specified solids interceptor is designed to be installed in lieu of the P-trap. Note also that the specified interceptor is designed for top access to the removable sediment bucket; install per the manufacturer's instructions to provide sufficient maintenance access. Reference: Sections 310.4 and 1001.1, UPC 2006. |
08/17/2010 | GERRY KOZIOL | WWM | REVIEW | Denied | need 5th floor credit evaluation |
08/25/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM02094 TI Dental 71111 E Tanque Verde 107 Electrical denied for following: 1. Circuit B 4,6 on AutoClave s/b A 4,6. 2. Circuit A 12,14 for dryer not on power plan. 3. Mark Circuit A 13 on Mech/Power plan. 4. Mark circuit #'s on AC units on Mech/Power Plan. 5. Mechanical Plan Reviewer requires that the exhaust fan in restroom be activated when ever air is supplied into restroom , not just when light on. Ray T Majuta PDSD, City of Tucson, Elect Pln Ck, 8/26/10 Ray.Majuta@tucsonaz.com |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/07/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
09/07/2010 | SUE REEVES | REJECT SHELF | Completed |