Permit Number: T10CM02094
Parcel: 11460019B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02094
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2010 TERRY STEVENS ZONING REVIEW Approved
07/30/2010 BIANCA RAMIREZ ENGINEERING REVIEW RECEIVED
07/30/2010 MARTIN BROWN FIRE REVIEW Approved
08/10/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. As per COT PDSD standards, minimum lettering type is 3/32" in height. The following sheets have lettering types less than 3/32": A1.1, A-2, H-1 and E5.1. Please revise all types to 3/32" minimum and resubmit
SHEET H-1
2. At detail 13, change the mounting height to the bottom of the main sign from 6'-8" to 7'-0"
3. As per Section 1210.2 Walls.
"Walls within 2 feet (610 mm) of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet (1219 mm) above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture."
a. the scheduled enamel paint is not hard and is adversly effected by moisture.
END OF REVIEW
08/10/2010 RONALD BROWN ZONING HC REVIEW Denied Reference Building Comments
08/11/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the outside air flow rate in keynote #1 on sheet M1.1 to agree with the outside air calculations.
2. Show the location of keynote #5, M1.1, on the drawing. Reference: Section 106.3.1, IMC 2006.
3. Revise the size of the condensate drains in accordance with Section 307.2.1, IMC 2006, as amended by the City of Tucson.
4. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. exhaust fans shall operate whenever supply air is being introduced into the restroom). Reference: Section 403.2.1 (4), IMC 2006.
08/11/2010 ROBERT SHERRY WATER REVIEW Approved
08/12/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. The plans have been reviewed to the 2006 UPC; provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC.
2. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for business occupancy (e.g. a service sink).
3. Provide a design for the mounting shelf for the water heater. Reference: Sections 310.0 and 314.5, UPC 2006.
4. Clarify how the temperature of the hot water supply to the public lavatories is to be controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
5. Provide pressure-absorbing devices for the water connections to appliances equipped with quick-acting or solenoid valves (e.g. clothes washer). Reference: Section 609.10, UPC 2006.
6. Verify that the reduced pressure backflow preventer located in room 114 conforms to the access and clearance requirements of Section 603.3.4, UPC 2006.
7. Provide a vacuum relief for storage-type water heaters located above any fixture outlets. Reference: Section 608.7, UPC 2006.
8. Provide cleanouts sized per Section 707.11, UPC 2006.
9. Revise waste and vent diagram "C" to correspond with the plumbing plan. Reference: Section 103.2.3, UPC 2006.
10. With respect to waste and vent diagram "D", no more than one trap shall be installed on a trap arm; the specified solids interceptor is designed to be installed in lieu of the P-trap. Note also that the specified interceptor is designed for top access to the removable sediment bucket; install per the manufacturer's instructions to provide sufficient maintenance access. Reference: Sections 310.4 and 1001.1, UPC 2006.
08/17/2010 GERRY KOZIOL WWM REVIEW Denied need 5th floor credit evaluation
08/25/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM02094
TI Dental
71111 E Tanque Verde 107

Electrical denied for following:
1. Circuit B 4,6 on AutoClave s/b A 4,6.
2. Circuit A 12,14 for dryer not on power plan.
3. Mark Circuit A 13 on Mech/Power plan.
4. Mark circuit #'s on AC units on Mech/Power Plan.
5. Mechanical Plan Reviewer requires that the exhaust fan in restroom be activated when ever air is supplied into restroom , not just when light on.

Ray T Majuta
PDSD, City of Tucson,
Elect Pln Ck,
8/26/10
Ray.Majuta@tucsonaz.com