Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM02090
Review Name: RESUBMITTAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
09/15/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
09/17/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the specification for the shower unit to be used in room 19; show that it meets the ADA requirements. 2. Provide a water riser diagram of the water distribution system to replace the water riser diagram that was deleted with sheet M8.2. Reference: Section 103.2.3, UPC 2006. 3. Revise the PEX tubing size chart shown on sheet M3.1. The flow rates shown for the ½", ¾" and 1" tubing water velocities all exceed 8 FPS and the demand associated with 32 fixture units is 21 GPM which will also result in a water velocity greater than 8 FPS in 1" PEX tubing. Reference: Sections 610.0 and 610.12, UPC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
09/21/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
09/21/2010 | SUE REEVES | REJECT SHELF | Completed |