Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM02090
Parcel: 110162770

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02090
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/15/2010 GERRY KOZIOL WWM REVIEW Approved
09/17/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the specification for the shower unit to be used in room 19; show that it meets the ADA requirements.
2. Provide a water riser diagram of the water distribution system to replace the water riser diagram that was deleted with sheet M8.2. Reference: Section 103.2.3, UPC 2006.
3. Revise the PEX tubing size chart shown on sheet M3.1. The flow rates shown for the ½", ¾" and 1" tubing water velocities all exceed 8 FPS and the demand associated with 32 fixture units is 21 GPM which will also result in a water velocity greater than 8 FPS in 1" PEX tubing. Reference: Sections 610.0 and 610.12, UPC 2006.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/21/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
09/21/2010 SUE REEVES REJECT SHELF Completed