Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2010 MARTIN BROWN FIRE REVIEW Denied This does not fit the definition for a "B" occupancy. Please revise Project Data and Code Check with corrected information.
08/05/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET A0.1
1. At the General Notes section change notes 1 and 2 to read City of Tucson instead of Pima County.
2. At note 21 change to read 2006 IBC, Chapter 11 and ICC (ANSI 117.1 2003 Edition). Delete the reference to "CABO ANSI 471 AS ADOPTED BY PIMA COUNTY".
3. At the Project Data and Code Check, change the occupancy classification from "B" to "I-2".
SHEET A2.1
4. As per 2006 IBC, Section 1109.2. "Toilet rooms ... shall be accessible". The following toilet rooms are not part of critical care or intensive care sleeping rooms and are not code compliant: 19, 22, 23 and 40. Please redesign and insure compliance with ICC (ANSI 117.1), Section 603.
5. As per the 2006 IBC, Section 1005.2, Doors opening into the path of egress travel shall not reduce the required width to less than one-half during the course of the swing. Non compliant doors are as follows: 8, 29, 33 and 46. Please redesign doors to comply with code and resubmit.
SHEET NOS. A2.1 AND MC-1
6. A point of use water dispenser is called out on sheet A2.1. As per COT Planning and Development Services Department policy adoption, a point of use water dispenser shall be the type that is permanently connected to a water supply source, a 1/4" water line. Pleas show location and water connection on sheet MC-1.
GENERAL
7. Please provide large scale partial floor plans and interior elevations of all different types of toilet rooms. Show all required dimensions and accessories necessary for accessibility compliance. Sheet G-2, a copy of the ANSI code showing generic details is not acceptable.
8. Please provide structural details and calculations for the new roof top mounted HVAC equipment.
END OF REVIEW
08/05/2010 RONALD BROWN ZONING HC REVIEW Denied Reference Building Comments
08/09/2010 ROBERT SHERRY WATER REVIEW Denied 1. Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 103.2.3, UPC 2006.
2. If the existing water meter serves more than just the tenant for the proposed tenant improvement activity, provide the total connected water demand that will result from the addition of this activity. Reference: Sections 610.1 and 610.2, UPC 2006.
08/10/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a copy of the approved drawings for the shell package of the building to establish the existing conditions of the tenant space and the shared plumbing systems. Reference: Sections 106.1 and 106.3, IBC 2006.
2. The branch piping sizes called out for the flush valves will result in water velocities greater than 8 FPS. Limit the water velocity to less than 8 FPS for the copper piping. Reference: Sections 610.12 and A 6.1, UPC 2006 and IS 3-2003, Section 2.6.
3. Provide end of run cleanout at mop sink, P-4. Reference: Section 707.4, UPC 2006.
4. Provide upper terminal cleanouts on horizontal drainage pipe over 5 feet in length (e.g. P-9-1, P-9-2). Reference: Section 707.4, UPC 2006.
08/10/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide a copy of the approved drawings for the shell package of the building to establish the existing conditions of the tenant space. Reference: Sections 106.1 and 106.3, IBC 2006.
2. Demonstrate energy code compliance. Reference: Section 101.4, International Energy Conservation Code 2006.
08/11/2010 LOREN MAKUS ENGINEERING REVIEW Approved Building pad 3+ feet above BFE.
08/16/2010 GERRY KOZIOL WWM REVIEW Denied need capcity evaluation by Kurt Stemm-3rd floor
08/20/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM02090
5979 E Grant RD #107
TI Medical Facility

Electrical Plans denied for following:

1. The exhaust fan on the lighting plan (restroom) should be numbered #3, is shown to be 115 volt on mechanical plans, and connected to a 277 volt circuit.
2. Circuit BC-36 to ex-fans #1 and #2 on power plan sheet should be going to Panel B.
3. Panel B circuit 42 on power plan to EDF should be circuit B-24.
4. Recept to bathroom B-2 to be GFI protected.

Ray T Majuta
PDSD City of Tuc,
8/22/10
Ray.Majuta@tucsonaz.gov