Permit Number: T10CM02060
Parcel: 12106001B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02060
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/23/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
08/23/2010 LOREN MAKUS ENGINEERING REVIEW Approved
08/23/2010 DAVE MANN FIRE REVIEW Approved
09/02/2010 ERIC NEWCOMB ADA REVIEW Passed
09/02/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/02/2010 ERIC NEWCOMB ZONING HC REVIEW Approved
09/02/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
09/07/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved Project 5851 E Speedway #141
T10CM02060


Electrical denied for following:

After an on site inspection, the existing space shows a 1200 amp CT can feeding an 800 amp disconnect to Appollo Carpet. The new office to be created is with in the space Appollo Carpet, therefore only one service is allowed per 2005 NEC-230-2 of the electrical code.



Ray T Majuta
PDSD City Of Tuc,
Elect Pln Ck
9/5/10
Ray.Majuta@tucsonaz.gov
10/12/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/12/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
10/12/2010 ROBERT SHERRY WATER REVIEW Approved
10/12/2010 GERRY KOZIOL WWM REVIEW Approved