Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM02053
Parcel: 117170110

Address:
135 S 6TH AV #A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02053
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2010 GERRY KOZIOL WWM REVIEW Denied need to provide plumbing schedule that includes ALL waste water fixtures that are going to be in suite with DWV sizes and isometric showing which fixtures are hooked up to grease interceptor and what fixtures drain indirectly.
needs WW credit evaluation-5th floor
needs IWC review/approval- Tom Tomchak, 579-5771- 5025 W Ina Rd
IWC: spray nozzel must be put on the wash compartment of 3-compartment sink
signs indicating"Hand Wash Only" above hand wash sinks- Doug Kirkland
08/19/2010 RMC CONSULTING BUILDING-COMMERCIAL REVIEW Approved
08/19/2010 RMC CONSULTING PLUMBING-COMMERCIAL REVIEW Approved
08/19/2010 RMC CONSULTING ELECTRICAL-COMMERCIAL REVIEW Approved
08/19/2010 RMC CONSULTING MECHANICAL-COMMERCIAL REVIEW Approved
08/20/2010 RMC CONSULTING HC REVIEW Passed Reviewed by Second Party: R. McCoy Consulting, Inc.
08/20/2010 ROBERT SHERRY WATER REVIEW Approved
08/23/2010 STEVE SHIELDS ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2010 GERARDO BONILLA OUT TO CUSTOMER Completed
08/31/2010 SUE REEVES REJECT SHELF Completed