Permit Number: T10CM02053
Parcel: 117170110

Address:
135 S 6TH AV #A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02053
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/27/2010 RMC CONSULTING BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. t10cm02053
R. McCoy Consulting Inc. Job No.TUC10-002

City of Tucson
201 N Stone Ave. 1st Floor
Tucson, AZ 85701

Re: Plan Review: Janos Downtown Restaurant
Address: 135 S. 6th Ave. # A


R. McCoy Consulting Inc. has completed a FIRST review of the following documents on behalf of the City of Tucson:

1. Plans: 1 copy of 25 sheets (A1.0 through e5.0) Stamped by Miguel R. Fuentevilla, Architect 07/20/2010. Mehrad Sadrisabet Mechanical Engineer 07/21/2010. Charles J Thompson Electrical Engineer 07/20/2010.


2. Lighting Specifications: One copy Columbia Lighting

These documents were reviewed only for their conformance to the provisions of the 2006 International Building Codes (i.e., State of Arizona and City of Tucson amended 2006 IBC, 2006 IMC, 2005 NEC and 2006 IPC).



Sincerely,
R. McCoy Consulting Inc.




Randy McCoy

ICC Plans Examiner
RMC skm



Janos Downtown Restaurant City of Tucson-First check
135 S. 6th Ave # A RMC job # TUC- 10 -002


General Comments:

1. Please amend the calculations for egress width per occupant served using the proper inches per occupant provided for a non sprinkled occupancy. 2006 IBC Table 1005.1

2. Please amend all noted code references to the 2006 Building Codes as noted in Project Data.

3. Please amend all noted references to Pima County to the City of Tucson.

4. Please change reference to the City of Scottsdale to the City of Tucson.


Plumbing comments:

1. Please amend grease Interceptor Sizing to reflect proper reference and sizing 2006 IPC table 1003.3.4.1.
07/27/2010 RMC CONSULTING MECHANICAL-COMMERCIAL REVIEW Denied CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. t10cm02053
R. McCoy Consulting Inc. Job No.TUC10-002

City of Tucson
201 N Stone Ave. 1st Floor
Tucson, AZ 85701

Re: Plan Review: Janos Downtown Restaurant
Address: 135 S. 6th Ave. # A


R. McCoy Consulting Inc. has completed a FIRST review of the following documents on behalf of the City of Tucson:

1. Plans: 1 copy of 25 sheets (A1.0 through e5.0) Stamped by Miguel R. Fuentevilla, Architect 07/20/2010. Mehrad Sadrisabet Mechanical Engineer 07/21/2010. Charles J Thompson Electrical Engineer 07/20/2010.


2. Lighting Specifications: One copy Columbia Lighting

These documents were reviewed only for their conformance to the provisions of the 2006 International Building Codes (i.e., State of Arizona and City of Tucson amended 2006 IBC, 2006 IMC, 2005 NEC and 2006 IPC).



Sincerely,
R. McCoy Consulting Inc.




Randy McCoy

ICC Plans Examiner
RMC skm



Janos Downtown Restaurant City of Tucson-First check
135 S. 6th Ave # A RMC job # TUC- 10 -002


General Comments:

1. Please amend the calculations for egress width per occupant served using the proper inches per occupant provided for a non sprinkled occupancy. 2006 IBC Table 1005.1

2. Please amend all noted code references to the 2006 Building Codes as noted in Project Data.

3. Please amend all noted references to Pima County to the City of Tucson.

4. Please change reference to the City of Scottsdale to the City of Tucson.


Plumbing comments:

1. Please amend grease Interceptor Sizing to reflect proper reference and sizing 2006 IPC table 1003.3.4.1.
07/27/2010 RMC CONSULTING ELECTRICAL-COMMERCIAL REVIEW Denied CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. t10cm02053
R. McCoy Consulting Inc. Job No.TUC10-002

City of Tucson
201 N Stone Ave. 1st Floor
Tucson, AZ 85701

Re: Plan Review: Janos Downtown Restaurant
Address: 135 S. 6th Ave. # A


R. McCoy Consulting Inc. has completed a FIRST review of the following documents on behalf of the City of Tucson:

1. Plans: 1 copy of 25 sheets (A1.0 through e5.0) Stamped by Miguel R. Fuentevilla, Architect 07/20/2010. Mehrad Sadrisabet Mechanical Engineer 07/21/2010. Charles J Thompson Electrical Engineer 07/20/2010.


2. Lighting Specifications: One copy Columbia Lighting

These documents were reviewed only for their conformance to the provisions of the 2006 International Building Codes (i.e., State of Arizona and City of Tucson amended 2006 IBC, 2006 IMC, 2005 NEC and 2006 IPC).



Sincerely,
R. McCoy Consulting Inc.




Randy McCoy

ICC Plans Examiner
RMC skm



Janos Downtown Restaurant City of Tucson-First check
135 S. 6th Ave # A RMC job # TUC- 10 -002


General Comments:

1. Please amend the calculations for egress width per occupant served using the proper inches per occupant provided for a non sprinkled occupancy. 2006 IBC Table 1005.1

2. Please amend all noted code references to the 2006 Building Codes as noted in Project Data.

3. Please amend all noted references to Pima County to the City of Tucson.

4. Please change reference to the City of Scottsdale to the City of Tucson.


Plumbing comments:

1. Please amend grease Interceptor Sizing to reflect proper reference and sizing 2006 IPC table 1003.3.4.1.
07/27/2010 DAVE MANN FIRE REVIEW Approved
07/27/2010 RMC CONSULTING PLUMBING-COMMERCIAL REVIEW Denied CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. t10cm02053
R. McCoy Consulting Inc. Job No.TUC10-002

City of Tucson
201 N Stone Ave. 1st Floor
Tucson, AZ 85701

Re: Plan Review: Janos Downtown Restaurant
Address: 135 S. 6th Ave. # A


R. McCoy Consulting Inc. has completed a FIRST review of the following documents on behalf of the City of Tucson:

1. Plans: 1 copy of 25 sheets (A1.0 through e5.0) Stamped by Miguel R. Fuentevilla, Architect 07/20/2010. Mehrad Sadrisabet Mechanical Engineer 07/21/2010. Charles J Thompson Electrical Engineer 07/20/2010.


2. Lighting Specifications: One copy Columbia Lighting

These documents were reviewed only for their conformance to the provisions of the 2006 International Building Codes (i.e., State of Arizona and City of Tucson amended 2006 IBC, 2006 IMC, 2005 NEC and 2006 IPC).



Sincerely,
R. McCoy Consulting Inc.




Randy McCoy

ICC Plans Examiner
RMC skm



Janos Downtown Restaurant City of Tucson-First check
135 S. 6th Ave # A RMC job # TUC- 10 -002


General Comments:

1. Please amend the calculations for egress width per occupant served using the proper inches per occupant provided for a non sprinkled occupancy. 2006 IBC Table 1005.1

2. Please amend all noted code references to the 2006 Building Codes as noted in Project Data.

3. Please amend all noted references to Pima County to the City of Tucson.

4. Please change reference to the City of Scottsdale to the City of Tucson.


Plumbing comments:

1. Please amend grease Interceptor Sizing to reflect proper reference and sizing 2006 IPC table 1003.3.4.1.
07/29/2010 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: janos DOWNTOWN
T10CM02053
Building Plan (1st Review)

TRANSMITTAL DATE: July 29, 2010

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Provide a copy of the last approved site plan with your next submittal.

3. The proposed outdoor seating shown along 6th is considered an expansion of use area. A site plan, meeting the requirements of D.S. 2-02, is required for the expansion.

4. The proposed outdoor seating shown along 6th appears to be within the right-of-way (ROW), contact COT Real Estate department and obtain permission to use the ROW area for seating.

5. A DRB may be required for this expansion, contact Russlyn Wells.

6. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

C:\planning\grading\t10cm02053.doc

RESUBMITTAL OF THE FOLLOWING IS REQUIRED:
08/05/2010 GERRY KOZIOL WWM REVIEW Denied need to provide plumbing schedule that includes all waste water fixtures that are going to be in suite, with DWV sizes and isometric showing which fixtures are hooked up to grease interceptor and what fixtures drain indirectly
need WW credit evaluation- 5th floor
need IWC review/approval- TomTomchak; 579-5771- 5025 W Ina Rd
08/05/2010 RMC CONSULTING ZONING HC REVIEW Denied CITY OF TUCSON - FIRST CHECK
Tucson Appl. No. t10cm02053
R. McCoy Consulting Inc. Job No.TUC10-002

City of Tucson
201 N Stone Ave. 1st Floor
Tucson, AZ 85701

Re: Plan Review: Janos Downtown Restaurant
Address: 135 S. 6th Ave. # A


R. McCoy Consulting Inc. has completed a FIRST review of the following documents on behalf of the City of Tucson:

1. Plans: 1 copy of 25 sheets (A1.0 through e5.0) Stamped by Miguel R. Fuentevilla, Architect 07/20/2010. Mehrad Sadrisabet Mechanical Engineer 07/21/2010. Charles J Thompson Electrical Engineer 07/20/2010.


2. Lighting Specifications: One copy Columbia Lighting

These documents were reviewed only for their conformance to the provisions of the 2006 International Building Codes (i.e., State of Arizona and City of Tucson amended 2006 IBC, 2006 IMC, 2005 NEC and 2006 IPC).



Sincerely,
R. McCoy Consulting Inc.




Randy McCoy

ICC Plans Examiner
RMC skm



Janos Downtown Restaurant City of Tucson-First check
135 S. 6th Ave # A RMC job # TUC- 10 -002


General Comments:

1. Please amend the calculations for egress width per occupant served using the proper inches per occupant provided for a non sprinkled occupancy. 2006 IBC Table 1005.1

2. Please amend all noted code references to the 2006 Building Codes as noted in Project Data.

3. Please amend all noted references to Pima County to the City of Tucson.

4. Please change reference to the City of Scottsdale to the City of Tucson.


Plumbing comments:

1. Please amend grease Interceptor Sizing to reflect proper reference and sizing 2006 IPC table 1003.3.4.1.
08/06/2010 ROBERT SHERRY WATER REVIEW Denied

Final Status

Task End Date Reviewer's Name Type of Review Description
08/10/2010 CPIERCE1 OUT TO CUSTOMER Completed
08/10/2010 SUE REEVES REJECT SHELF Completed