Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM02053
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/27/2010 | RMC CONSULTING | BUILDING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON - FIRST CHECK Tucson Appl. No. t10cm02053 R. McCoy Consulting Inc. Job No.TUC10-002 City of Tucson 201 N Stone Ave. 1st Floor Tucson, AZ 85701 Re: Plan Review: Janos Downtown Restaurant Address: 135 S. 6th Ave. # A R. McCoy Consulting Inc. has completed a FIRST review of the following documents on behalf of the City of Tucson: 1. Plans: 1 copy of 25 sheets (A1.0 through e5.0) Stamped by Miguel R. Fuentevilla, Architect 07/20/2010. Mehrad Sadrisabet Mechanical Engineer 07/21/2010. Charles J Thompson Electrical Engineer 07/20/2010. 2. Lighting Specifications: One copy Columbia Lighting These documents were reviewed only for their conformance to the provisions of the 2006 International Building Codes (i.e., State of Arizona and City of Tucson amended 2006 IBC, 2006 IMC, 2005 NEC and 2006 IPC). Sincerely, R. McCoy Consulting Inc. Randy McCoy ICC Plans Examiner RMC skm Janos Downtown Restaurant City of Tucson-First check 135 S. 6th Ave # A RMC job # TUC- 10 -002 General Comments: 1. Please amend the calculations for egress width per occupant served using the proper inches per occupant provided for a non sprinkled occupancy. 2006 IBC Table 1005.1 2. Please amend all noted code references to the 2006 Building Codes as noted in Project Data. 3. Please amend all noted references to Pima County to the City of Tucson. 4. Please change reference to the City of Scottsdale to the City of Tucson. Plumbing comments: 1. Please amend grease Interceptor Sizing to reflect proper reference and sizing 2006 IPC table 1003.3.4.1. |
| 07/27/2010 | RMC CONSULTING | MECHANICAL-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON - FIRST CHECK Tucson Appl. No. t10cm02053 R. McCoy Consulting Inc. Job No.TUC10-002 City of Tucson 201 N Stone Ave. 1st Floor Tucson, AZ 85701 Re: Plan Review: Janos Downtown Restaurant Address: 135 S. 6th Ave. # A R. McCoy Consulting Inc. has completed a FIRST review of the following documents on behalf of the City of Tucson: 1. Plans: 1 copy of 25 sheets (A1.0 through e5.0) Stamped by Miguel R. Fuentevilla, Architect 07/20/2010. Mehrad Sadrisabet Mechanical Engineer 07/21/2010. Charles J Thompson Electrical Engineer 07/20/2010. 2. Lighting Specifications: One copy Columbia Lighting These documents were reviewed only for their conformance to the provisions of the 2006 International Building Codes (i.e., State of Arizona and City of Tucson amended 2006 IBC, 2006 IMC, 2005 NEC and 2006 IPC). Sincerely, R. McCoy Consulting Inc. Randy McCoy ICC Plans Examiner RMC skm Janos Downtown Restaurant City of Tucson-First check 135 S. 6th Ave # A RMC job # TUC- 10 -002 General Comments: 1. Please amend the calculations for egress width per occupant served using the proper inches per occupant provided for a non sprinkled occupancy. 2006 IBC Table 1005.1 2. Please amend all noted code references to the 2006 Building Codes as noted in Project Data. 3. Please amend all noted references to Pima County to the City of Tucson. 4. Please change reference to the City of Scottsdale to the City of Tucson. Plumbing comments: 1. Please amend grease Interceptor Sizing to reflect proper reference and sizing 2006 IPC table 1003.3.4.1. |
| 07/27/2010 | RMC CONSULTING | ELECTRICAL-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON - FIRST CHECK Tucson Appl. No. t10cm02053 R. McCoy Consulting Inc. Job No.TUC10-002 City of Tucson 201 N Stone Ave. 1st Floor Tucson, AZ 85701 Re: Plan Review: Janos Downtown Restaurant Address: 135 S. 6th Ave. # A R. McCoy Consulting Inc. has completed a FIRST review of the following documents on behalf of the City of Tucson: 1. Plans: 1 copy of 25 sheets (A1.0 through e5.0) Stamped by Miguel R. Fuentevilla, Architect 07/20/2010. Mehrad Sadrisabet Mechanical Engineer 07/21/2010. Charles J Thompson Electrical Engineer 07/20/2010. 2. Lighting Specifications: One copy Columbia Lighting These documents were reviewed only for their conformance to the provisions of the 2006 International Building Codes (i.e., State of Arizona and City of Tucson amended 2006 IBC, 2006 IMC, 2005 NEC and 2006 IPC). Sincerely, R. McCoy Consulting Inc. Randy McCoy ICC Plans Examiner RMC skm Janos Downtown Restaurant City of Tucson-First check 135 S. 6th Ave # A RMC job # TUC- 10 -002 General Comments: 1. Please amend the calculations for egress width per occupant served using the proper inches per occupant provided for a non sprinkled occupancy. 2006 IBC Table 1005.1 2. Please amend all noted code references to the 2006 Building Codes as noted in Project Data. 3. Please amend all noted references to Pima County to the City of Tucson. 4. Please change reference to the City of Scottsdale to the City of Tucson. Plumbing comments: 1. Please amend grease Interceptor Sizing to reflect proper reference and sizing 2006 IPC table 1003.3.4.1. |
| 07/27/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/27/2010 | RMC CONSULTING | PLUMBING-COMMERCIAL | REVIEW | Denied | CITY OF TUCSON - FIRST CHECK Tucson Appl. No. t10cm02053 R. McCoy Consulting Inc. Job No.TUC10-002 City of Tucson 201 N Stone Ave. 1st Floor Tucson, AZ 85701 Re: Plan Review: Janos Downtown Restaurant Address: 135 S. 6th Ave. # A R. McCoy Consulting Inc. has completed a FIRST review of the following documents on behalf of the City of Tucson: 1. Plans: 1 copy of 25 sheets (A1.0 through e5.0) Stamped by Miguel R. Fuentevilla, Architect 07/20/2010. Mehrad Sadrisabet Mechanical Engineer 07/21/2010. Charles J Thompson Electrical Engineer 07/20/2010. 2. Lighting Specifications: One copy Columbia Lighting These documents were reviewed only for their conformance to the provisions of the 2006 International Building Codes (i.e., State of Arizona and City of Tucson amended 2006 IBC, 2006 IMC, 2005 NEC and 2006 IPC). Sincerely, R. McCoy Consulting Inc. Randy McCoy ICC Plans Examiner RMC skm Janos Downtown Restaurant City of Tucson-First check 135 S. 6th Ave # A RMC job # TUC- 10 -002 General Comments: 1. Please amend the calculations for egress width per occupant served using the proper inches per occupant provided for a non sprinkled occupancy. 2006 IBC Table 1005.1 2. Please amend all noted code references to the 2006 Building Codes as noted in Project Data. 3. Please amend all noted references to Pima County to the City of Tucson. 4. Please change reference to the City of Scottsdale to the City of Tucson. Plumbing comments: 1. Please amend grease Interceptor Sizing to reflect proper reference and sizing 2006 IPC table 1003.3.4.1. |
| 07/29/2010 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: janos DOWNTOWN T10CM02053 Building Plan (1st Review) TRANSMITTAL DATE: July 29, 2010 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Provide a copy of the last approved site plan with your next submittal. 3. The proposed outdoor seating shown along 6th is considered an expansion of use area. A site plan, meeting the requirements of D.S. 2-02, is required for the expansion. 4. The proposed outdoor seating shown along 6th appears to be within the right-of-way (ROW), contact COT Real Estate department and obtain permission to use the ROW area for seating. 5. A DRB may be required for this expansion, contact Russlyn Wells. 6. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site plan. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\grading\t10cm02053.doc RESUBMITTAL OF THE FOLLOWING IS REQUIRED: |
| 08/05/2010 | GERRY KOZIOL | WWM | REVIEW | Denied | need to provide plumbing schedule that includes all waste water fixtures that are going to be in suite, with DWV sizes and isometric showing which fixtures are hooked up to grease interceptor and what fixtures drain indirectly need WW credit evaluation- 5th floor need IWC review/approval- TomTomchak; 579-5771- 5025 W Ina Rd |
| 08/05/2010 | RMC CONSULTING | ZONING HC | REVIEW | Denied | CITY OF TUCSON - FIRST CHECK Tucson Appl. No. t10cm02053 R. McCoy Consulting Inc. Job No.TUC10-002 City of Tucson 201 N Stone Ave. 1st Floor Tucson, AZ 85701 Re: Plan Review: Janos Downtown Restaurant Address: 135 S. 6th Ave. # A R. McCoy Consulting Inc. has completed a FIRST review of the following documents on behalf of the City of Tucson: 1. Plans: 1 copy of 25 sheets (A1.0 through e5.0) Stamped by Miguel R. Fuentevilla, Architect 07/20/2010. Mehrad Sadrisabet Mechanical Engineer 07/21/2010. Charles J Thompson Electrical Engineer 07/20/2010. 2. Lighting Specifications: One copy Columbia Lighting These documents were reviewed only for their conformance to the provisions of the 2006 International Building Codes (i.e., State of Arizona and City of Tucson amended 2006 IBC, 2006 IMC, 2005 NEC and 2006 IPC). Sincerely, R. McCoy Consulting Inc. Randy McCoy ICC Plans Examiner RMC skm Janos Downtown Restaurant City of Tucson-First check 135 S. 6th Ave # A RMC job # TUC- 10 -002 General Comments: 1. Please amend the calculations for egress width per occupant served using the proper inches per occupant provided for a non sprinkled occupancy. 2006 IBC Table 1005.1 2. Please amend all noted code references to the 2006 Building Codes as noted in Project Data. 3. Please amend all noted references to Pima County to the City of Tucson. 4. Please change reference to the City of Scottsdale to the City of Tucson. Plumbing comments: 1. Please amend grease Interceptor Sizing to reflect proper reference and sizing 2006 IPC table 1003.3.4.1. |
| 08/06/2010 | ROBERT SHERRY | WATER | REVIEW | Denied |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/10/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 08/10/2010 | SUE REEVES | REJECT SHELF | Completed |