Permit Number: T10CM02039
Parcel: 10511061G

Address:
4620 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM02039
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/31/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
09/01/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved. The structural calculations are based on a Douglas fir 2"x 6" studs instead of the steel studs being used for the wall and the combined weight of the hood and a person working on the hood is not presented. Un-sealed shop drawing may not be substituted for sealed structural details. Provide structural calculations and details to show that the Type I and Type II hoods are supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.
09/02/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The trash enclosure trench drain installation, shown on the utility site plans calls for a 320-gallon gravity grease interceptor and references the plumbing drawings for design of the required vent. The minimum size for a gravity grease interceptor is 500-gallons (for up to 8 drainage fixture units). No vent information was found on the plumbing drawings but the 4" building sewer called out on the site utility drawing is shown as a 6" building sewer on sheet P-2. Reference: Sections 103.2.3 and 1014.3.6, UPC 2006.
09/02/2010 ERIC NEWCOMB HC REVIEW Approved
09/02/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
09/07/2010 DAVID RIVERA ZONING REVIEW Approved
09/09/2010 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
09/21/2010 GERARDO BONILLA OUT TO CUSTOMER Completed