Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM02012
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2010 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 07/21/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | . |
| 07/21/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 07/21/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/21/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. PROVIDE ACCESSIBILITY DETAILS FOR THE TRANSFER-TYPE SHOWER ON THE FULL SIZE DRAWINGS PER THE ICC/ANSI A117.1-2003, SECTION 608. 2. PROVIDE NOTES ON THE DRAWINGS CONCERNING EXISTING PLUMBING ELEMENTS, SUCH AS THE SERVICE SINK, RESTROOMS, AND DRINKING FOUNTAINS. |
| 07/21/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 07/21/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a comparison of the water heater being replaced with of the new water heater with regard to the weight and dimensions (i.e. is the existing platform capable of supporting the new water ) 2. Provide a vacuum relief for the water heater. 3. Show the pipe sizes in detail 3/P1.1. |
| 07/21/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 07/21/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/21/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Denied | 1. SEE BUILDING COMMENT. |
| 07/21/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/22/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |