Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM02012
Parcel: 140260360

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM02012
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
07/21/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved .
07/21/2010 ERIC NEWCOMB ADA REVIEW Passed
07/21/2010 ROBERT SHERRY WATER REVIEW Approved
07/21/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PROVIDE ACCESSIBILITY DETAILS FOR THE TRANSFER-TYPE SHOWER ON THE FULL SIZE DRAWINGS PER THE ICC/ANSI A117.1-2003, SECTION 608.
2. PROVIDE NOTES ON THE DRAWINGS CONCERNING EXISTING PLUMBING ELEMENTS, SUCH AS THE SERVICE SINK, RESTROOMS, AND DRINKING FOUNTAINS.
07/21/2010 GERRY KOZIOL WWM REVIEW Approved
07/21/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a comparison of the water heater being replaced with of the new water heater with regard to the weight and dimensions (i.e. is the existing platform capable of supporting the new water )
2. Provide a vacuum relief for the water heater.
3. Show the pipe sizes in detail 3/P1.1.
07/21/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
07/21/2010 MARTIN BROWN FIRE REVIEW Approved
07/21/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENT.
07/21/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/22/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved