Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM01985
Parcel: 10820051G

Address:
4036 N 1ST AV

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01985
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/05/2010 MARTIN BROWN FIRE REVIEW Approved
08/09/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL:
1. As per COT standards, all plans require a minimum of 3/32" type.
a. The following sheets have been noted as having type less than 3/32": G0.1, I1.1, E0.1, E0.2, EM1, R1, R2, R4, I1.0, I1.3.2, I2.1, I2.2, I2.3 and I2.4.
b. Please revise all sheets to meet the minimum standard type size and resubmit.
SHEET A1.1
2. Please provide an elevation of the new beverage center counter to show compliance with 2006 IBC, ICC (ANSI 117.1), Section 904.
SHEET 4.1
3. Generic details are not acceptable. Please provide all accessibility dimensions and requirements on the actual design floor plan and elevations.
4. At elevation 12D:
a. A sanitary napkin disposal receptical is keynoted in the men's accessible toilet stall while none is noted in the women's stall.
b. It appears that keynotes "M" and "G" may be reversed.
c. The universal accessible symbol located at the top of the mirror is keynoted as "6", Not Used.
5. Elevation "A" and Detail 30 shows keynote "M" and "G" perhaps reversed.
6. Identify the toilet accessory mounted on the North partition of both accessible toilet stalls. It is identified as "P" in detail 30, Not Used.
7. Please review all keynotes as to accuracy and resubmit. If accessory items are actually "Not To Be Used" then please eleminate them from the details and resubmit.
END OF REVIEW
08/10/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
08/10/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide additional cleanouts in drainage pipe for each aggregate horizontal change of direction exceeding 135 degrees. Reference: Sections 707.5 and 707.7, UPC 2006.
2. Provide cleanouts sized per Section 707.11, UPC 2006
08/10/2010 ROBERT SHERRY WATER REVIEW Approved
08/10/2010 RONALD BROWN ZONING HC REVIEW Denied Reference Building Comments
08/10/2010 PAUL MACHADO ENGINEERING REVIEW Approved
08/24/2010 GERRY KOZIOL WWM REVIEW Approved
08/26/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project:T10CM01985
4036 N 1ST AV
Fry's Remodel

Electrical plans denied for following:

1. City Commercial Submittal Requirements, all submittals to be min 3/32' font,
2. Provide a fixture schedule showing wattage of lamp , type of lamp , and mounting type .

Ray T Majuta
PDSD, City of Tucson,
Elect Plan Review,
8/29/10
Ray.Majuta@tucsonaz.gov
08/27/2010 TERRY STEVENS ZONING REVIEW Approved