Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM01985
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/05/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
08/09/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | GENERAL: 1. As per COT standards, all plans require a minimum of 3/32" type. a. The following sheets have been noted as having type less than 3/32": G0.1, I1.1, E0.1, E0.2, EM1, R1, R2, R4, I1.0, I1.3.2, I2.1, I2.2, I2.3 and I2.4. b. Please revise all sheets to meet the minimum standard type size and resubmit. SHEET A1.1 2. Please provide an elevation of the new beverage center counter to show compliance with 2006 IBC, ICC (ANSI 117.1), Section 904. SHEET 4.1 3. Generic details are not acceptable. Please provide all accessibility dimensions and requirements on the actual design floor plan and elevations. 4. At elevation 12D: a. A sanitary napkin disposal receptical is keynoted in the men's accessible toilet stall while none is noted in the women's stall. b. It appears that keynotes "M" and "G" may be reversed. c. The universal accessible symbol located at the top of the mirror is keynoted as "6", Not Used. 5. Elevation "A" and Detail 30 shows keynote "M" and "G" perhaps reversed. 6. Identify the toilet accessory mounted on the North partition of both accessible toilet stalls. It is identified as "P" in detail 30, Not Used. 7. Please review all keynotes as to accuracy and resubmit. If accessory items are actually "Not To Be Used" then please eleminate them from the details and resubmit. END OF REVIEW |
08/10/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
08/10/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide additional cleanouts in drainage pipe for each aggregate horizontal change of direction exceeding 135 degrees. Reference: Sections 707.5 and 707.7, UPC 2006. 2. Provide cleanouts sized per Section 707.11, UPC 2006 |
08/10/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
08/10/2010 | RONALD BROWN | ZONING HC | REVIEW | Denied | Reference Building Comments |
08/10/2010 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
08/24/2010 | GERRY KOZIOL | WWM | REVIEW | Approved | |
08/26/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project:T10CM01985 4036 N 1ST AV Fry's Remodel Electrical plans denied for following: 1. City Commercial Submittal Requirements, all submittals to be min 3/32' font, 2. Provide a fixture schedule showing wattage of lamp , type of lamp , and mounting type . Ray T Majuta PDSD, City of Tucson, Elect Plan Review, 8/29/10 Ray.Majuta@tucsonaz.gov |
08/27/2010 | TERRY STEVENS | ZONING | REVIEW | Approved |