Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM01979
Parcel: 12410504A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01979
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2010 STEVE SHIELDS ZONING REVIEW Approved
07/16/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/16/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
07/16/2010 ROBERT SHERRY WATER REVIEW Approved
07/16/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
07/16/2010 JASON GREEN ENGINEERING REVIEW Approved
07/16/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/16/2010 DAVE MANN FIRE REVIEW Approved
07/16/2010 RONALD BROWN ADA REVIEW Passed
07/16/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/16/2010 RONALD BROWN ZONING HC REVIEW Approved
07/21/2010 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/21/2010 SUE REEVES OUT TO CUSTOMER Completed