Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM01944
Parcel: 10509546C

Address:
68 W RIVER RD

Review Status: Completed

Review Details: OTHER

Permit Number - T10CM01944
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide storm water drain cleanouts at intervals no greater than 100 feet for straight runs and for aggregate horizontal changes of direction of 135 degrees or greater. Reference: Sections 719.1 and 1101.12.1, UPC 2006.
2. Clarify the sizing of the horizontal storm water piping under the canopy and show how the rainwater leaders are to connect to the SDR 35 PVC horizontal storm water piping. Note that the PVC rain water leaders are required to be schedule 40 per Section 1102.0, UPC 2006.