Permit Number: T10CM01943
Parcel: 10509546C

Address:
68 W RIVER RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM01943
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/07/2010 STEVE SHIELDS ZONING REVIEW Denied 12/07/2010

Development Services Department
Zoning Review Section

Terry Stevens
Lead Planner

Comments:

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcomin
12/08/2010 MARTIN BROWN FIRE REVIEW Approved
12/09/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/10/2010 GERRY KOZIOL WWM REVIEW Approved
12/10/2010 CPIERCE1 PLUMBING-COMMERCIAL REVIEW Needs Review
12/10/2010 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/06/2011 SUE REEVES APPROVAL SHELF Completed
01/06/2011 CINDY AGUILAR OUT TO CUSTOMER Completed