Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T10CM01942
Parcel: 128050130

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T10CM01942
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/31/2011 GERRY KOZIOL WWM REVIEW Approved
01/31/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the model number for the mop sink, P4. It appears to be a floor-mounted mop basin with the trap below grade but the riser diagram appears to show it roughed in above grade.
2. Provide upper terminal cleanouts (required for all directly-connected sinks).
3. Provide a riser diagram clarifying the installation of sink P5.
4. Clarify the water riser diagram; the tempered water is not shown.
5. Clarify the water pressure calculations: your calculations show that a 1" meter with a 1-1/4" service pipe is required but you state that the existing 5/8" meter and 1" service pipe is to remain.
01/31/2011 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
01/31/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
01/31/2011 ROBERT SHERRY WATER REVIEW Denied Verify the presence of a backflow preventer for the water service.
01/31/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Clarify the installation of the back-supply duct plenum, i.e. show how it is to be installed in compliance with the manufacturer's instructions.
2. Clarify the size of the hood - it is shown as 4'-6" and called out as 3'-0" and 4'-0' .
3. Show that the wall behind the hood meets the clearance requirements of Section 507.9, IMC 2006.
01/31/2011 ERIC NEWCOMB ADA REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
02/28/2011 SUE REEVES OUT TO CUSTOMER Completed