Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T10CM01942
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/31/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/31/2011 | GERRY KOZIOL | WWM | REVIEW | Approved | |
| 01/31/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the model number for the mop sink, P4. It appears to be a floor-mounted mop basin with the trap below grade but the riser diagram appears to show it roughed in above grade. 2. Provide upper terminal cleanouts (required for all directly-connected sinks). 3. Provide a riser diagram clarifying the installation of sink P5. 4. Clarify the water riser diagram; the tempered water is not shown. 5. Clarify the water pressure calculations: your calculations show that a 1" meter with a 1-1/4" service pipe is required but you state that the existing 5/8" meter and 1" service pipe is to remain. |
| 01/31/2011 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 01/31/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 01/31/2011 | ROBERT SHERRY | WATER | REVIEW | Denied | Verify the presence of a backflow preventer for the water service. |
| 01/31/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Clarify the installation of the back-supply duct plenum, i.e. show how it is to be installed in compliance with the manufacturer's instructions. 2. Clarify the size of the hood - it is shown as 4'-6" and called out as 3'-0" and 4'-0' . 3. Show that the wall behind the hood meets the clearance requirements of Section 507.9, IMC 2006. |
| 01/31/2011 | ERIC NEWCOMB | ADA | REVIEW | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/28/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |