Permit Number: T10CM01914
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01914
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
07/12/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-0.1; CODE INFORMATION: THE ACCESSIBILITY CODE IS ICC/ANSI A117.1-2003. CHANGE NOTE.
2. GENERAL: PROVIDE INFORMATION ON THE DRAWINGS INDICATING THE TRAVEL DISTANCE TO THE EXISTING ACCESSIBLE RESTROOMS AND DRINKING FOUNTAINS.
3. GENERAL: SHEET A-1.2: A MINIMUM LETTERING HEIGHT OF 3/32" IS REQUIRED ON ALL DRAWINGS.
07/14/2010 RSHERRY1 WWM REVIEW Passed No new plumbing fixtures.
07/14/2010 ROBERT SHERRY WATER REVIEW Approved
07/14/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/14/2010 MARTIN BROWN FIRE REVIEW Approved
07/14/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/14/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM01914,
5870 E Broadway, #302, LensCrafters,

1. Name the circuits the new Track Lighting will be and verfy the existing circuits can handle the new loads.
2. Show the location of the Panel and identfy the new circuits, and provide new loads plus existing loads. A panel schedule would provide the information needed..

Ray T Majuta, Elect Pln Ck
PDSD,City of Tucson,
7/14/10
Ray.Majuta@tucsonaz.gov
07/15/2010 JASON GREEN ENGINEERING REVIEW Approved
07/15/2010 TERRY STEVENS ZONING REVIEW Approved