Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T10CM01887
Parcel: 11942006E

Review Status: Completed

Review Details: POST 3RD PARTY REVIEW

Permit Number - T10CM01887
Review Name: POST 3RD PARTY REVIEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
08/24/2010 MARTIN BROWN FIRE REVIEW Denied Fire access lanes required to be 20 wide unobstructed. The islands on the NW turn around appear to impinge on the 20'.
Fire Department approved lock boxes will be needed at gates.
No Parking - Fire Lane signs will be needed. Sign detail on page x1.3 is incorrect.
Exiting diagrams are confusing (sheet g1.8). Sometimes exit numbers seem to exceed 50, but panic hardware is not provided. Door swings may be incorrect.
It appears there is a stove in kitchen. This would require a type 1 hood, with suppression system.
08/25/2010 MATT FLICK ENGINEERING REVIEW Needs Review
08/25/2010 SREEVES1 WWM REVIEW Needs Review
08/25/2010 ROBERT SHERRY WATER REVIEW Approved