Review Details: REVISION - - 1ST

Permit Number - T10CM01881
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/14/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project:T10CM01881 Revision 1
4362 N Oracle Rd
(Revise Service from 600 A 277/480 V to
2000 A 120/208 V)

The electrical plans have been denied for the following:

1. Provide fault current calculations for the new 2000 A
service on to the owners panels.
2. The lighting used is different from the lighting submitted for the first plan, please provide an up- dated calculation for
City's Outdoor Light Ord, 10035.
3. Clarify the circuit loads for Panel OWSB circuits 1 and 2. The lighting plan appears to show 1.2 A(amps?) for each sign control location, the panel schedule only shows 200 va's.

Ray T Majuta,PDSD, City of Tuc,
Elect Pln Ck,
10/14/10