Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM01881
Parcel: 105110700

Address:
4362 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM01881
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/16/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
08/17/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied The vent required under Section 904.1 provides ventilation of the building sewer (i.e. the pipe from the connection to the public sewer to the termination of the building drain). The vent must be connected to the building sewer downstream of the backwater valve. Adding a vent to the building drain does not provide the required ventilation.