| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/16/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 08/17/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | The vent required under Section 904.1 provides ventilation of the building sewer (i.e. the pipe from the connection to the public sewer to the termination of the building drain). The vent must be connected to the building sewer downstream of the backwater valve. Adding a vent to the building drain does not provide the required ventilation. |