Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM01881
Parcel: 105110700

Address:
4362 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL NEW

Permit Number - T10CM01881
Review Name: COMMERCIAL NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/20/2010 DAVE MANN FIRE REVIEW Approved
07/23/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide deferred submittal summary letter to Mr. LeeRay Hanly for additional fee accessment.
2. Please provide Special Inspector CertificationS for appoval.
3. Calculations sheet 5 calls for DB-9 as TS 6 x 3 x 3/16 @ 8' o.c. whereas the drawings do not size these steel trusses at all.
4. Calculations call for DJ3 to be TS 2 x 2 x 3/16 and drawings do not size these joists at all.
5. At sheet S2.0, C3 is scheduled to be a 2x2x3/16 and the calculations do not show this size anywhere. All plan referenced C-3s should be C-1s?
6. Foundation Plan schedules F3 as 5' square w/ 7#5s whereas the calculations calls for (DF-1) as 6' square w/6#5s. Please clearify.
7. Ditto comment 6 above for Drawing ftg F3 shows 5' square w/7 #5; calculations call for it (DF-3) as 6' square w/ 6#5s. Please calrify
8. Ditto comment 6 above for Drawing ftg F3 shows 5' square w/7 #5; calculations call for it (DF-5) as 6' square w/ 6#5s. Please calrify.
9. There are no calculations for detail 1/S3.1, BREREZEWAY CANOPY FRAMING PLAN. Please clarify.
10. Please review further calculations for drawing coordinations; Bond beam and lintel sizing, Lateral and Shear Wall Design, Wall design, Lateral analysis and Shear wall footing and grade beam design.
11. Further comments may be comming after review of corrected resubmittal.
END OF REVIEW
07/26/2010 RONALD BROWN HC REVIEW Passed
07/27/2010 GERRY KOZIOL WWM REVIEW Approved
08/03/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
08/03/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide vent piping of sufficient size for the building sewer to comply with Section 904.1, UPC 2006. Vents located upstream from pumps, ejectors, backwater valves, or other devices that obstruct the free flow of gases between the building sewer and the outside atmosphere shall not be used for meeting the required cross-sectional vent area.
08/03/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
08/03/2010 ROBERT SHERRY WATER REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/16/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
08/16/2010 SUE REEVES REJECT SHELF Completed