01/03/2011 ANDREW CONNOR LANDSCAPE REVIEW Needs Review See comments from last review
01/05/2011 LOREN MAKUS ENGINEERING REVIEW Needs Review
12/17/2010 DAVE MANN FIRE REVIEW Approved
12/20/2010 RONALD BROWN ZONING HC REVIEW Approved
12/27/2010 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: River Valley Rance
T10CM01877
Site Plan (4th Review)

TRANSMITTAL DATE: December 27, 2010

COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Provide a response letter with your next submittal.

2. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC) for full code compliance for a change of use.

3. The provided lot coverage calculation does not appear to be correct. For example; Driveway show "PROPOSED DRIVEWAY: 3,260 SQ. FT.". Using an average width driveway width of 12' this square foot would allow for approximately 271 lf of drive. As scaled off the provided drawing the western most drive from the right-of-way line to the "COVERED PARKING TO BE PERMITED" well over 480'. The provided driveway calculation does not appear to include the driveway to the proposed SFR or STEEL BUILDING. The "PARKING AREA" square footage under "AREA CALCULATIONS" shows 14,000 sq. ft. and the square footage of the "PARKING AREA" shown on the plan shows 18,800. The "TRAILER PARKING" appears to only show the area for parking but no maneuvering in to the parking spaces. D.S. 2-02.2.2.A.3 The proposed lot coverage exceeds the allowed for the proposed use in an SR zone. A Board of Adjustment for Variance is required to exceed the lot coverage.

4. D.S. 2-02.2.1.A.12 Provide a keynote on the site plan stating "No Vehicle Access" signs to be provide at these locations and show the locations on the plan.

5. Depending on how the above comments are addressed addition comments may be forth coming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956.

C:\planning\site\t10cm01877

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/05/2011 DELMA ROBEY OUT TO CUSTOMER Completed