Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T10CM01870
Parcel: 135076890

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01870
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2010 DAVE MANN FIRE REVIEW Approved
07/14/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET X1; CODE ANALYSIS: NOTE 14 CONCERNING EXIT ACCESS TRAVEL DISTANCE REFERENCES TABLE 1015.1. REVISE TO IBC TABLE 1016.1. VERIFY.
2. SHEET X1; CODE ANALYSIS: NOTE 1 REFERENCES AMERICAN'S WITH DISABILITIES ACT OF 1990. REVISE ACCESSIBILITY REFERENCE TO ICC/ANSI A117.1-2003. VERIFY.
3. SHEET A0; ELEVATION L: THE HEIGHT OF THE COUNTER MUST MEET ACCESSIBILITY REQUIREMENTS PER IBC CHAPTER 9 (34" MAXIMUM HEIGHT). VERIFY.
4. SHEET A0; WALL/PARTITION TYPES: PROVIDE A DETAIL FOR THE BRACING OF THE TOP OF INTERIOR PARTITIONS TO MEET IBC SECTION 1607.13, INCLUDING BRACE SIZE AND SPACING, BRACE CONNECTION TO THE EXISTING STRUCTURE, AND BRACE CONNECTION TO THE TOP OF THE PARTITION.
5. SHEET A4; DOOR SCHEDULE: DID NOT LOCATE DOOR HARDWARE SET SCHEDULE. VERIFY.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
07/16/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENTS.
07/21/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/21/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/22/2010 ROBERT SHERRY WATER REVIEW Denied Seven buildings on this site are served by a common 2" water meter; provide the total demand for the site and show that the additional connections do not cause the existing water meter or piping to be overloaded. Note that Tucson Water limits 2" water meters to a maximum demand of 80 GPM. Reference: Section 101.5.1, UPC 2006.
07/30/2010 RMC CONSULTING ELECTRICAL-COMMERCIAL REVIEW Approved
07/30/2010 GERRY KOZIOL WWM REVIEW Denied NEED TO PROVIDE APPROVAL TO DISCHARGE TO PRIVATE ON-SITE SEWER
NEEDS TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER- CONTACT KURT STEMM 3RD FLOOR -740-6607

Final Status

Task End Date Reviewer's Name Type of Review Description
08/05/2010 CPIERCE1 OUT TO CUSTOMER Completed
08/05/2010 SUE REEVES REJECT SHELF Completed