Permit Number: T10CM01866
Parcel: 105102520

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM01866
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/30/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Show how adequate maintenance access will be provided for the water heater.
07/30/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the design of the interlock between the exhaust fan and the A/C unit; the electrical design appers to be no more than a copy of the mechanical note.
08/04/2010 DROBEY1 WWM REVIEW Needs Review
08/04/2010 DROBEY1 ELECTRICAL-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/04/2010 DELMA ROBEY OUT TO CUSTOMER Completed