Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM01866
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/30/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Show how adequate maintenance access will be provided for the water heater. |
| 07/30/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify the design of the interlock between the exhaust fan and the A/C unit; the electrical design appers to be no more than a copy of the mechanical note. |
| 08/04/2010 | DROBEY1 | WWM | REVIEW | Needs Review | |
| 08/04/2010 | DROBEY1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/04/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |