Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2010 MICHAEL ST. PAUL ZONING REVIEW Approved
07/08/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a design showing how the restroom exhaust fan is to be interlocked with the indoor fan of HP-1.
07/08/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Needs Review
07/08/2010 ROBERT SHERRY WATER REVIEW Approved
07/08/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEETS A-101 AND P-201: THE DRINKING FOUNTAIN MUST BE A HIGH/LOW MODEL OR A SINGLE POINT-OF-USE STYLE TO MEET ACCESSIBILITY REQUIREMENTS.
07/08/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
07/08/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide information to show how the proposed water heater platform is to be supported from the building structure. Reference: Section 314.5, UPC 2006.
07/08/2010 DAVE MANN FIRE REVIEW Approved
07/08/2010 ERIC NEWCOMB ADA REVIEW Passed
07/08/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
07/08/2010 ERIC NEWCOMB ZONING HC REVIEW Denied 1. SEE BUILDING COMMENT.
07/13/2010 CPIERCE1 WWM REVIEW Needs Review