Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: CELL TOWER/ANTENNAS
Permit Number - T10CM01863
Review Name: CELL TOWER/ANTENNAS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/08/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/09/2010 | Michael Wyneken | PLANNING-CITY HALL | REVIEW | Denied | Add notes, as necessary, regarding painting equipment per conditions f and g. |
| 07/13/2010 | BRIAN HEFFERNAN | COMMUNICATIONS | REVIEW | Approved | |
| 07/19/2010 | ELIZABETH EBERBACH | ENGINEERING | REVIEW | Denied | DATE: July 20, 2010 SUBJECT: Cricket Antennae & Cabinet Plan Engineering Review ADDRESS: 2501 N Flowing Wells Rd LOCATION: T13S R13E Section 35 REVIEWER: Elizabeth Leibold ACTIVITY NUMBER: T10CM01863 SUMMARY: The Cricket antennae & cabinet plans at the Flowing Wells Electrical Power site were submitted to the City of Tucson for review. It is understood that this project will consist of upgrading communications equipment. The project is located in a regulatory floodplain - Krueger Wash flood area which is a City of Tucson Flood Hazard area. Planning & Development Services Department PDSD Engineering has reviewed the received items and does not recommend approval of the plan/permit without addressing the following comments. PLAN COMMENTS: 1) DS Sec.10-02.2.2.5: Floodplain Use Permit is required for this project. Submit City of Tucson's Floodplain Use Permit Application. 2) DS Sec.10-02.2.1.3: Provide a drainage statement that addresses the following comments in the statement and on the plans: a) On sheet T-1, there is a statement that the Pinal County Flood Control District approved the flood depth. Please clarify/correct PCRFCD name to Pima County. b) DS Sec.10-02.2.1.3: Provide documentation showing flood depth from regional flood control district as noted on plans. c) Tucson Code Sec. 26-11.2(a)(1): The datum for the water surface elevation and FFE of the pad foundation shall be the same; indicate datum for cabinet foundation pad elevation and 100-year flood WSEL. d) Tucson Code 26-5.2(11): The cabinet structure upgrades are subject to minimum FFE elevations. Show floodproofing for the structure on the plans if the cabinets are below 100-yr WSEL. 3) Add note to sheet C-3 that: no new electrical equipment shall be placed below Regulatory Flood Elevation (which is 1-foot above the 100-year water surface elevation). It will be necessary to provide the floodplain use permit application with resubmittal. Please address all comments prior to resubmittal and if you have questions, call me at 837-4934. Elizabeth Leibold, PE Civil Engineer Engineering Division Planning & Development Services Department |
| 07/23/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/27/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 07/28/2010 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: T10CM01863 2501 N. Flowing Wells Road (1st Review) TRANSMITTAL DATE: July 28, 2010 1. The Cell Tower plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. The plan must be approved and stamped by the Special Exception Section prior to approval by Zoning. 3. Zoning will re-review the Cell Tower plan on the next submittal to insure compliance with the approved Special Exception process. Additional comments may be forthcoming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 C:\planning\celltower\t10cm01863.doc |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/06/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 08/06/2010 | SUE REEVES | REJECT SHELF | Completed |