Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM01853
Parcel: 13629003A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01853
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. At details D/H1, D/H2, D/H3 and all associated plans, provide a ramp and a 3' deep detectable warning strip at the East side of the marked crossings as per ADAAG, Sections 4.7 and 4.29.5.
2. Please provide a written deferred submittal summary listing to Mr. LeeRay Hanly for additional fee accessment.
3. Please provide structural calculations for the lightuing pole foundations.
4. At sheet PP1, details A/H1, A/H2 and A/H3 provide an accessible passenger loading zone at station 0+00 as per ADAAG, Section 4.6.6.
5. Please show the loactions of the "No H/C" signs on all plans.
6. Please insure that structural foundation plans and structural calculations are included with the Ramada deferred
submittal.
END OF REVIEW
07/09/2010 DAVE MANN FIRE REVIEW Approved
07/09/2010 RONALD BROWN ADA REVIEW Denied Reference Building Comments
07/12/2010 ANDREW CONNOR LANDSCAPE REVIEW Denied 1. All development within Regulated Areas must comply with all other applicable code provisions, including obtaining floodplain use permits where necessary. Washes zoned or named in the WASH regulations must also be reviewed in conformance with the DSD Full Notice Procedure, Sections 23A- 50 and 51 DS 9-06.2.7

2. If encroachment is proposed into the Regulated Area(s), submittal of an Environmental Resource Report in conformance as defined in LUC 6.2.5 & DS 9-06.2.5.B.1 is required.

3. Include with re-submittal overlay case approval documentation. Indicate on the lower right hand corner of the site plan, the case number, date of approval, and any conditions imposed. Site plan review will continue once DSD Full Notice Procedure is complete.
07/14/2010 ANDREW CONNOR NPPO REVIEW Denied 1. All development within Regulated Areas must comply with all other applicable code provisions, including obtaining floodplain use permits where necessary. Washes zoned or named in the WASH regulations must also be reviewed in conformance with the DSD Full Notice Procedure, Sections 23A- 50 and 51 DS 9-06.2.7

2. If encroachment is proposed into the Regulated Area(s), submittal of an Environmental Resource Report in conformance as defined in LUC 6.2.5 & DS 9-06.2.5.B.1 is required.

3. Include with re-submittal overlay case approval documentation. Indicate on the lower right hand corner of the site plan, the case number, date of approval, and any conditions imposed. Site plan review will continue once DSD Full Notice Procedure is complete.
07/23/2010 ROBERT SHERRY WATER REVIEW Passed
07/23/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
07/23/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
07/28/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PP E1.3, PLEASE PROVIDE CONDUCTOR & CONDUIT INFORMATION FOR CIRCUIT FROM SES TO NEW LIGHT.

PP E1.3, PLEASE PROVIDE PANEL SCHEDULE FOR SES, OR KEYNOTE AS TO WHICH SPARE CKT'S TO USE IN PANEL.

PP E1.4 DETAIL 2 REFERENCES A DETAIL S01 FOR THE LIGHT POLE BASE WHICH DOES NOT EXIST. PLEASE NOTE MAXIMUM HEIGHT ABOVE GRADE FOR LUMINAIRE AND PROVIDE STRUCTURAL INFORMATION FOR BASE.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/05/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
08/05/2010 SUE REEVES REJECT SHELF Completed