Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T10CM01836
Review Name: OTHER
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/07/2010 | ROBERT SHERRY | WATER | REVIEW | Denied | A demand flow of 25 GPM through a 5/8" water meter (Tucson Water does not provide ¾" meters) results in an excessive pressure drop and a velocity greater than the maximum 8 FPS allowed for either plastic or copper piping. In addition, Tucson Water limits the 5/8" meter to a maximum demand of 10 GPM. Reference: Sections 610.2 and 610.12, UPC 2006. |
| 07/21/2010 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/28/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 07/28/2010 | SUE REEVES | REJECT SHELF | Completed |