Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10CM01836
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/07/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the size of the grease ducts for KH-1 and KH-2 to provide a minimum velocity of 1500 feet per minute. Reference: Section 506.3.4, IMC 2006, as amended by the City of Tucson. 2. Clarify the reason for having backdraft dampers supplied with EF-1, EF-2, and EF-3. Reference: Section 106.3.1, IMC 2006. 3. Clarify the source of the occupancy rate and outdoor air requirement for the retail space as shown in the outside air calculations on sheet M1. Reference: Section 403.3, IMC 2006. |
| 07/07/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Verify that the Pima County Regional Wastewater Reclamation Department will not require the floor sink (P1) that is serving the sanitizing compartment of the 3-compartment sink (15) to be connected to the gravity grease interceptor. 2. The grease interceptor sizing calculation shown on sheet P1 is part of an adopted policy of the Pima County Chief Building Official (September 2, 2009) that has not been adopted by the City of Tucson. The City of Tucson operates under the 2006 UPC; the size of gravity grease interceptors shall be determined per Section 1014.3.6.1, UPC 2006 unless an appeal to the building official is made under Section 301.2, UPC 2006. The drainage fixture units used for the calculation shall be determined per Table 7-3, UPC 2006. 3. Coordinate the waste and vent isometric (A/P2) with the plumbing waste and gas floor plan (2/P1) by showing the vent for the gravity grease interceptor on A/P2. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/28/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 07/28/2010 | SUE REEVES | REJECT SHELF | Completed |