| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/06/2010 | DAVE MANN | FIRE | REVIEW | Approved | |
| 07/16/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/16/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | PROJECT: 1650 W Valencia Walmart , T10CM01814 The Electrical Plans have been denied for the following: 1. Sheet E-4 shows Transformer T4D(150 kva) feeding a disconnect ECB-L4D3-1, with 4-250mcm cu & #4 grd,The disconnect should be fused at 225 amps. 2. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/19/2010 | SUE REEVES | OUT TO CUSTOMER | Completed |