Permit Number: T10CM01814
Parcel: 129020470

Review Status: Completed

Review Details: COMMERCIAL-BLDG/FIRE/ZONING/ENG

Permit Number - T10CM01814
Review Name: COMMERCIAL-BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/06/2010 DAVE MANN FIRE REVIEW Approved
07/16/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved PROJECT: 1650 W Valencia
Walmart , T10CM01814


The Electrical Plans have been denied for the following:

1. Sheet E-4 shows Transformer T4D(150 kva) feeding a disconnect ECB-L4D3-1, with 4-250mcm cu & #4 grd,The disconnect should be fused at 225 amps.
2.
07/16/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/19/2010 SUE REEVES OUT TO CUSTOMER Completed