Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T10CM01810
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/19/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | Floor elevation of pump room changed. |
| 11/22/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/22/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET S-1.11 (DETAIL 15); SHEET S-2.11B: DETAIL 15 INDICATES THE TOP OF THE ELEVATOR PIT SLAB IS 5'-0" MAX. BELOW THE FINISHED FLOOR, WHILE SHEET S-2.11B INDICATES THE TOP OF THE ELEVATOR PIT SLAB IS 5'-6" BELOW THE FINISHED FLOOR. CLARIFY. 2. SHEET S-1.11; DETAIL 20: WHAT IS THE 3'-4" PORTION OF WALL? SHOULD THIS DETAIL BE SIMILAR TO DETAIL 15/S-1.11? CLARIFY. 3. SHEET S-1.41 (DETAIL 5); STRUCTURAL CALCULATIONS (PAGE 60): THE STRUCTURAL CALCULATIONS INDICATE HSS 4X3X3/8 FRAME (FULL HEIGHT), WHILE THE DETAIL INDICATES HSS 4X3X3/16 FOR THE UPPER PORTION OF THE FRAME. CLARIFY. 4. SHEET S-1.41 (DETAIL 15); SHEETS S-2.11A AND S-2.11B: DID NOT FIND A DETAIL 15 REFERENCE ON THE PLAN SHEETS. VERIFY. 5. SHEET S-2.11A; PLAN: IT APPEARS STEPS HAVE BEEN ADDED TO THE MOMENT FRAME FOUNDATION, NOT ELIMINATED PER THE REVISION NARRATIVE. CLARIFY. 6. SHEET S-2.11B; PLAN: IT APPEARS STEPS HAVE BEEN ADDED TO THE MOMENT FRAME FOUNDATION, NOT ELIMINATED PER THE REVISION NARRATIVE. CLARIFY. 7. SHEET A-2.1; PLAN: THIS SHEET SHOULD BE REVISED TO INDICATE THE DIMENSION CHANGE BETWEEN GRIDS 1.9 AND 2. VERIFY. 8. SHEET S-2.11A (PLAN); SHEET P-2.1 (PLUMBING GROUND FLOOR PLAN): VERIFY THE FINISH FLOOR ELEVATION AT THE PUMP ROOM. THE STRUCTURAL SHEET INDICATES TOC EL 0'-0", WHILE THE PLUMBING SHEET HAS A NOTE INDICATING 96.7. 9. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/02/2010 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |
| 12/02/2010 | SUE REEVES | REJECT SHELF | Completed |