Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM01807
Parcel: 11460019B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01807
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/01/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
07/01/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied PP T1--CORRECT CODE REVIEW TO INDICATE THAT RESTAURANTS ARE AN A2 OCCUPANCY AND NOT THE M NOTED.

PP T1---CURRENT EDITION OF THE IFC IS THE 2006 NOT THE 2003 NOTED

PP T1--WE DO NOT USE THE CITY OF GLENDALE ZONING ORDINANCE TITLE 17 FOR ANYTHING.

PP T1-- UNIT 7111-A REQUIRES 2 EXITS FOR OCCUPANT LOAD OVER 50. ONLY 1 NOTED.

PP A1-- DETAIL 3 HAS A DETAIL REFERENCE TO 5/A2. THERE IS NO DETAIL 5 ON PP A2

PP A1 -- SPECIFY "ACOUSTICAL SEALANT" AT TOP OF WALL FOR RATED FIRE BARRIERS. NEEDS TO BE RATED FOR FIRE ASSEMBLIES.
07/01/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/01/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PLANS INCOMPLETE FOR WORK INDICATED
07/01/2010 ROBERT SHERRY WATER REVIEW Approved
07/01/2010 DAVE MANN FIRE REVIEW Denied Fire Comments:

Travel distance cannot exceed 75 feet. See IFC Table 1019.2.
07/01/2010 TERRY STEVENS ZONING REVIEW Approved
07/12/2010 GBONILL1 WWM REVIEW Needs Review
07/12/2010 GBONILL1 ZONING HC REVIEW Needs Review
07/12/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
07/12/2010 GBONILL1 ADA REVIEW Needs Review