Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL TI
Permit Number - T10CM01807
Review Name: COMMERCIAL TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/01/2010 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 07/01/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 07/01/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Denied | PLANS INCOMPLETE FOR WORK INDICATED |
| 07/01/2010 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 07/01/2010 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Denied | PP T1--CORRECT CODE REVIEW TO INDICATE THAT RESTAURANTS ARE AN A2 OCCUPANCY AND NOT THE M NOTED. PP T1---CURRENT EDITION OF THE IFC IS THE 2006 NOT THE 2003 NOTED PP T1--WE DO NOT USE THE CITY OF GLENDALE ZONING ORDINANCE TITLE 17 FOR ANYTHING. PP T1-- UNIT 7111-A REQUIRES 2 EXITS FOR OCCUPANT LOAD OVER 50. ONLY 1 NOTED. PP A1-- DETAIL 3 HAS A DETAIL REFERENCE TO 5/A2. THERE IS NO DETAIL 5 ON PP A2 PP A1 -- SPECIFY "ACOUSTICAL SEALANT" AT TOP OF WALL FOR RATED FIRE BARRIERS. NEEDS TO BE RATED FOR FIRE ASSEMBLIES. |
| 07/01/2010 | BIANCA RAMIREZ | ENGINEERING | REVIEW | Approved | |
| 07/01/2010 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 07/01/2010 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: Travel distance cannot exceed 75 feet. See IFC Table 1019.2. |
| 07/12/2010 | GBONILL1 | WWM | REVIEW | Needs Review | |
| 07/12/2010 | GBONILL1 | ADA | REVIEW | Needs Review | |
| 07/12/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 07/12/2010 | GBONILL1 | ZONING HC | REVIEW | Needs Review |