Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2010 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
07/12/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/12/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10CM01805
TI SHELL REMODEL
7111 E TANQUE VERDE

1. The plans, Sheet E-1 and E-2, must show spaces addressed as Suites 101,107,and 113 as shown on permit application. The main disconnects must also relect this.
2. The feeder from the TEP transformer to the new 600 amp service shows only 2 sets of 4- 3/0,s foe 400 amps, should be 3 sets.
3. The grounding systems for both services are to be bonded together.


Ray T Majuta,PDSD,City of Tuc.,
7/12/10, Elect Pln Ck,