| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/12/2010 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 07/12/2010 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 07/12/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10CM01805 TI SHELL REMODEL 7111 E TANQUE VERDE 1. The plans, Sheet E-1 and E-2, must show spaces addressed as Suites 101,107,and 113 as shown on permit application. The main disconnects must also relect this. 2. The feeder from the TEP transformer to the new 600 amp service shows only 2 sets of 4- 3/0,s foe 400 amps, should be 3 sets. 3. The grounding systems for both services are to be bonded together. Ray T Majuta,PDSD,City of Tuc., 7/12/10, Elect Pln Ck, Ray.Majuta@tucsonaz.gov |
| 07/12/2010 | ERIC NEWCOMB | ZONING HC | REVIEW | Approved | |
| 07/12/2010 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 07/13/2010 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/26/2010 | CPIERCE1 | WWM | REVIEW | Needs Review |