Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10CM01805
Parcel: 11460019B

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01805
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2010 TERRY STEVENS ZONING REVIEW Approved
07/01/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
07/01/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Denied PLANS INCOMPLETE FOR WORK INDICATED
07/01/2010 ROBERT SHERRY WATER REVIEW Approved
07/01/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Denied PP T1--CORRECT CODE REVIEW TO INDICATE THAT RESTAURANTS ARE AN A2 OCCUPANCY AND NOT THE M NOTED.

PP T1---CURRENT EDITION OF THE IFC IS THE 2006 NOT THE 2003 NOTED

PP T1--WE DO NOT USE THE CITY OF GLENDALE ZONING ORDINANCE TITLE 17 FOR ANYTHING.

PP T1-- UNIT 7111-A REQUIRES 2 EXITS FOR OCCUPANT LOAD OVER 50. ONLY 1 NOTED.

PP A1-- DETAIL 3 HAS A DETAIL REFERENCE TO 5/A2. THERE IS NO DETAIL 5 ON PP A2

PP A1 -- SPECIFY "ACOUSTICAL SEALANT" AT TOP OF WALL FOR RATED FIRE BARRIERS. NEEDS TO BE RATED FOR FIRE ASSEMBLIES.
07/01/2010 BIANCA RAMIREZ ENGINEERING REVIEW Approved
07/01/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
07/01/2010 DAVE MANN FIRE REVIEW Denied Fire Comments:

Travel distance cannot exceed 75 feet. See IFC Table 1019.2.
07/12/2010 GBONILL1 WWM REVIEW Needs Review
07/12/2010 GBONILL1 ADA REVIEW Needs Review
07/12/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
07/12/2010 GBONILL1 ZONING HC REVIEW Needs Review