Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10CM01801
Parcel: 11901076A

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T10CM01801
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. The applicable code for all commercial plumbing projects is the 2006 Uniform Plumbing Code with Local Amendments. The water calculations on sheet P-6 state that they are based on "Appendix A of the 6 IPC" but they appear to be from Appendix A of the UPC. Provide an approved appeal to the building official if the plans are to be reviewed to the 2006 IPC.
3. Provide the minimum plumbing facilities (e.g. a drinking fountain) required by Table 2902.1 and Section 2902.2, IBC 2006, for a business occupancy. See also Section 1109.5, IBC 2006.
4. Provide a copy of the approved drawings for the shell package of the building to establish the existing conditions of the tenant space and the shared plumbing systems (e.g. are the two restrooms new or existing) Reference: Sections 106.1 and 106.3, IBC 2006.
5. Provide a design for the installation of the water heaters along with structural calculations to show that the water heaters are safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
6. Provide reference specifications and listing information for the lint interceptor, LT-1. Reference: Sections 103.2.3 and 1012.1, UPC 2006.
7. Provide calculations to show that the expansion tank, ET-1 is adequate for the proposed hot water system. Reference: Section 103.2.3, UPC 2006.
8. Coordinate the water heating portion of the hot and cold water isometric with the hot water heater piping diagram on sheet P-4. Reference: Section 103.2.3, UPC 2006.
9. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
10. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length); see FS-1 and MS-1. Reference: Section 707.4, UPC 2006.
11. Revise note 2 for the gas isometric detail and the regulator schedule (GR-2) on sheet P-5 to coordinate with the scheduled gas inputs for the water heaters.
12. Size natural gas pipe per Section 1217.1, UPC 2006 or provide calculations demonstrating conformance to Section 1217.3, UPC 2006. The low-pressure piping to the two water heaters appears to be undersized and the medium-pressure gas main (3202 CFH) also appears to be undersized.
07/12/2010 ROBERT SHERRY WATER REVIEW Denied Tucson Water limits a 2" meter to a maximum demand of 80 GPM. Provide a letter from Tucson Water confirming that the use of a 2" water meter will be allowed for this project (423 fixture units equates to a demand of 109 GPM). Reference: Sections 610.2 and 610.12, UPC 2006.
07/13/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008).
2. Provide a copy of the approved drawings for the shell package of the building to establish the existing conditions of the tenant space. Reference: Sections 106.1 and 106.3, IBC 2006.
3. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top units. Reference: Section 302.1, IMC 2006.
4. Show the size, routing, and termination of the condensate drains. Reference: Section 307.2, IMC 2006 and Section 814.0, UPC 2006.
5. Provide calculations demonstrating adequate ventilation. Reference: Section 401.2, IMC 2006.
6. Specify the minimum resistance (R-value) of the duct insulation to be used on this project. Reference: Section 503.2.7, IECC 2006, as amended by the City of Tucson.
07/14/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied GENERAL
1. Please indicate accessible code, 2006 IBC, Chapter 11 and ICC (ANSI 117.1 2003 Edition), in the code list summary.
a. Please Delete the "ADA" reference on all sheets and reference the above stated governing accessibility code.
2. Please provide structueral calculations for all roof top mounted HVAC equipment and the two new roof top mounted water heaters.
SHEET A-2
3. Clarify the difference between a partition that is poche'd to a partition that is not poche'd.
4. Please provide a wall section throught the toilet room and the office?
5. What is the circled equipment referenced number 11?
6. Please provide drinking fountains as per 2006 IBC Section 1109.5.1 and ICC, Section 602.
SHEET A-3
7. Reference comment 1 above.
8. Show plumbing fixture clearences as required by
ICC, Section 6.
9. Please provide vertical grab bar as per ICC, Section 604.5.1
END OF REVIEW
07/15/2010 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
07/15/2010 RONALD BROWN ZONING HC REVIEW Denied reference Commercial - Building comments
07/22/2010 GERRY KOZIOL WWM REVIEW Denied NEED TYPE III SEWER CAPACITY LETTER (3RD FLOOR- KURT STEMM 740-6607)
NEED TO UPDATE DP WITH REVISED FIXTURE UNITS
NEED TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER
NEED CONSTRUCTION AUTHORIZATION FROM P.D.E.Q. (BANK OF AMERICA BLDG- 7TH FLOOR)
07/23/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
07/30/2010 CPIERCE1 OUT TO CUSTOMER Completed
07/30/2010 SUE REEVES REJECT SHELF Completed