Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T10CM01795
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/08/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. On Sheet Nos 8006 (2 of 3 and 3 of 3), E085 and E802; the strair rise of 12'-6" is not compliant with the 2006 IBC, Section 1009.6.
2. On Sheet E079, Stair Plan - Roof Level L-10, stair One does not have a landing section showing the top landing return rail to the wall as stair no two, Section "A", on sheet E092. Please provide same.
a. The section references on the same stair one landing area to Sheets E079, E155 and E054 are erroneous. These sheets are not available in the submittal.
END OF REVIEW