Permit Review Detail
Review Status: Completed
Review Details: REVISION - - 1ST
Permit Number - T10CM01795
Review Name: REVISION - - 1ST
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/08/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. On Sheet Nos 8006 (2 of 3 and 3 of 3), E085 and E802; the strair rise of 12'-6" is not compliant with the 2006 IBC, Section 1009.6. 2. On Sheet E079, Stair Plan - Roof Level L-10, stair One does not have a landing section showing the top landing return rail to the wall as stair no two, Section "A", on sheet E092. Please provide same. a. The section references on the same stair one landing area to Sheets E079, E155 and E054 are erroneous. These sheets are not available in the submittal. END OF REVIEW |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/16/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |
| 12/16/2010 | SUE REEVES | REJECT SHELF | Completed |