Permit Number: T10CM01790
Parcel: 13216600A

Review Status: Completed

Review Details: OTHER

Permit Number - T10CM01790
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
06/30/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Verify that the specified piping materials conform to the requirements of Section 1202, IMC 2006.
2. Verify that the existing expansion tank can accomodate the additional volume of the expanded heating system. Refrence: Section 1009, IMC 2006.
3. Verify that the specified pipe insulation complies with the requirements of Section 503.2.8, IMC 2006.