Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T10CM01790
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/30/2010 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
06/30/2010 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Verify that the specified piping materials conform to the requirements of Section 1202, IMC 2006. 2. Verify that the existing expansion tank can accomodate the additional volume of the expanded heating system. Refrence: Section 1009, IMC 2006. 3. Verify that the specified pipe insulation complies with the requirements of Section 503.2.8, IMC 2006. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
07/12/2010 | GERARDO BONILLA | OUT TO CUSTOMER | Completed |