Permit Number: T10CM01771
Parcel: 13612001N

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM01771
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed; second request. Provide energy code compliance calculations using the correct climate zone (Pima County < 4,000 feet). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Comment not resolved; second request. Schedule of diffusers has been changed to eliminate all diffusers except "D". Coordinate the schedule of diffusers and registers (M601) with the duct layout on sheet M101. Reference: Section 106.3.1, IMC 2006.
10/12/2010 RONALD BROWN HC REVIEW Denied Reference Building Comments
10/12/2010 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied Non Responsive to previous review comment:
3. On Sheet A211, generic accessibility details are not acceptable. Please provide all accessibility code requirements on the actual floor plan and elevations.
10/19/2010 GERRY KOZIOL WWM REVIEW Denied need approved development plan
need approval to discharge by PCRWRD or hold harmless letter per CC Patel 2nd floor
need PMOC to public sewer. Public sewer plans have not been permitted- see Kurt Stemm

Final Status

Task End Date Reviewer's Name Type of Review Description
12/02/2010 DELMA ROBEY OUT TO CUSTOMER Completed
12/02/2010 SUE REEVES REJECT SHELF Completed