Permit Number: T10CM01771
Parcel: 13612001N

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T10CM01771
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2010 STEVE SHIELDS ZONING REVIEW Approved
09/30/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
09/30/2010 CPIERCE1 HC REVIEW Needs Review
09/30/2010 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
09/30/2010 JASON GREEN ENGINEERING REVIEW Approved
09/30/2010 CPIERCE1 WWM REVIEW Needs Review
09/30/2010 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide energy code compliance calculations using the correct climate zone (Pima County < 4,000 feet). Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections 101.4 and 104.2, International Energy Conservation Code 2006.
2. Comment not resolved; schedule of diffusers has been changed to eliminate all diffusers except "D". Coordinate the schedule of diffusers and registers (M601) with the duct layout on sheet M101. Reference: Section 106.3.1, IMC 2006.